The MCL-400IR+ Digital Ior Leakage Current Clamp Tester is designed to measure resistive leakage current (Ior) in low-voltage electrical circuits. Unlike conventional leakage current clamp meters that measure total leakage current (Io), the MCL-400IR+ enables measurement of the resistive component without requiring a voltage input for phase detection. This capability supports insulation condition assessment while the electrical circuit remains energized.
The tester provides AC current measurement ranges from 40 mA to 300 A, AC voltage measurement up to 500 V, and a 40 mm clamp opening. It also includes harmonic current and voltage measurement capabilities, with specified accuracy for the fundamental and selected harmonics up to the 13th order.
Accuracy Specifications
Accuracy conditions: 23℃±5℃, 80%RH or less (50/60Hz)
| Function | Range | Resolution | Accuracy |
|---|---|---|---|
| AC Current (ACA) | 40mA | 0.01mA | ±1.0% rdg ±8 dgt |
| 400mA | 0.1mA | ±1.0% rdg ±8 dgt | |
| 4A | 0.001A | ±1.0% rdg ±8 dgt | |
| 40A | 0.01A | ±1.0% rdg ±8 dgt | |
| 300A | 0.1A | ±1.0% rdg ±1% FS | |
| AC Voltage (ACV) | 500V | 0.1V | ±1.0% rdg ±8 dgt |
Harmonic Current and Voltage Accuracy Specifications
| Function | Harmonic Order | Accuracy |
|---|---|---|
| Harmonic Current and Voltage | Fundamental, 3rd, 5th, 7th | ±1% rdg ±5 dgt ±AC current and voltage accuracy |
| 11th, 13th | ±2% rdg ±5 dgt ±AC current and voltage accuracy |
Note: Minimum fundamental input current: more than 2% of each current.
Key Features of MCL-400IR+ Digital Ior Leakage Current Clamp Tester
- Resistive Leakage Current (Ior) Measurement: Measures the resistive component of leakage current without requiring voltage input for phase detection.
- AC Current Measurement: Five measurement ranges covering 40 mA, 400 mA, 4 A, 40 A, and 300 A.
- AC Voltage Measurement: Supports AC voltage measurement up to 500 V.
- Harmonic Measurement: Provides harmonic current and voltage measurement with specified accuracy for the fundamental and 3rd, 5th, 7th, 11th, and 13th harmonics.
- 40 mm Clamp Opening: Features a Ø40 mm current transformer opening for clamping around conductors.
Documents
Instruction Manual: e-ma-MCL-400IR+.pdf
Additional Information
Measuring method: |
Dual slope integration mode |
Display: |
3.5 digit LCD, max. reading of 4000 |
Measuring ranges: |
AC 0-40mA, 400mA, 4A, 40A, 300A, || AC 0~500V |
AC Conversion: |
Average sensing rms reading |
Input Frequency: |
45-65Hz |
Influence of external magnetic field: |
Less than 5mA (nearby 100A conductor) |
Inside diameter of CT: |
φ40mm |
Withstanding voltage: |
AC 2200V/1 minute |
Limitation of circuit voltage: |
Less than AC 500V |
Over range indication: |
"OL" mark on LCD |
Data hold indication: |
"DH" mark on LCD |
Low battery indication: |
"Battery" icon on LCD |
Sampling rate: |
2 times/sec |
Storage temperature: |
-10~60℃, < 70%RH (without condensation) |
Power supply: |
1.5V ("AAA" sixe, um-4)x3 |
Dimension: |
70(W)×223(H)×34(D)mm |
Accessories: |