M-2100+ Digital Clamp Meter for AC Current, AC/DC Voltage and Resistance

The MULTImic M-2100+ Digital Clamp Meter is a multifunctional measuring instrument designed for AC current measurement up to 2000 A. It features a wide, teardrop-shaped 55 mm diameter clamp opening for measuring high AC currents. The meter also supports AC/DC voltage and resistance measurements, diode testing, and continuity checks. Its data hold and automatic power-off functions provide added convenience for electrical testing and maintenance applications.

Accuracy Specifications

Function Range Accuracy Maximum Input / Protection
AC Current (50/60 Hz), Manual Ranging 20 A ±1.2% rdg ± 10 dgt AC 2000 A (within 3 seconds)
200 A ±1.2% rdg ± 10 dgt
2000 A ±1.2% rdg ± 8 dgt
AC Voltage (50/60 Hz) / DC Voltage, Auto Ranging 2 V ±0.7% rdg ± 5 dgt DC 750 V or AC 750 V RMS
20 V ±1.2% rdg ± 5 dgt
200 V ±1.2% rdg ± 5 dgt
750 V ±1.2% rdg ± 5 dgt
Resistance (Ω), Auto Ranging 200 Ω ±1.2% rdg ± 5 dgt Input protection: 250 V RMS (within 10 seconds)
2 kΩ ±1.2% rdg ± 5 dgt
20 kΩ ±1.2% rdg ± 5 dgt
200 kΩ ±1.2% rdg ± 5 dgt
2000 kΩ ±1.2% rdg ± 5 dgt
20 MΩ ±3.0% rdg ± 10 dgt
Continuity Check 200 Ω Beeper sounds below approximately 50 Ω 250 V RMS
Diode Test 2 V ±10% rdg ± 3 dgt 250 V RMS

Key Features of M-2100+ Digital Clamp Meter

  • AC current measurement with 20 A, 200 A, and 2000 A ranges
  • Wide 55 mm diameter teardrop-shaped clamp opening
  • AC voltage measurement
  • DC voltage measurement
  • Resistance measurement
  • Diode test function
  • Continuity check function
  • Data hold function for retaining measurement readings
  • Automatic power-off function
  • Conforms to IEC safety requirements, as specified by the manufacturer

Documents

Catalog: e_ca_m2100+.pdf

Instruction Manual: e_ma_m-M-2100+.pdf

View AllClose

Additional Information

Withstanding Voltage:
AC 3700V 1 minute max. (Between the core of CT and outer case)
Storage Temperature:
-10℃ to 60℃, 70%RH max. ( Without condensation )
Accuracy:
See accuracy specifications in description tab
Operating Temperature:
0℃ to 40℃, 80%RH max. ( Without condensation )
Power supply:
1.5V (AM-4, LR03 or AAA)×2
Power consumption:
3.5mW
Safety standard:
IEC 61010-1, IEC 61010-2-032 Installation CategoryⅡ600V or CategoryⅢ300V.
Jaw opening capability:
55mmφ
Size:
85(W)×240(H)×34(D)mm
Accessories:
Hard carrying case | Instruction manual | Test lead | Batteries Accuracy
Display:
3.5 digit LCD, max. reading of 1999
Over range indication:
Blanking of all digits except MSD 1
Data hold indication:
"DH" mark on LCD
Low battery indication:
"Battery" mark on LCD
Auto power off:
Automatically turned off if the meter has not been used for approx. 10 minutes.
E.M.C. standard:
EN 61326
Measuring method:
Dual slope integration mode
Battery life:
Approx. 500 hours continuous
Sampling:
2 times/sec