HCL-7000DX-M Digital Clamp Current Tester for Medium Voltage

The HCL-7000DX-M Digital Clamp Current Tester is designed for AC load current measurement on medium-voltage overhead distribution lines and the primary side of transformers. It features automatic range selection of 20 A, 200 A and 600 A, a 35 mm CT inside diameter, and a maximum circuit voltage of AC 23 kV when connected to a hot stick longer than 1 m.

Measurement readings can be viewed directly on the built-in LCD or remotely via Bluetooth using a dedicated MDU series display unit. Designed as a successor to the HCL-5000 series, HCL-9000 series and HCL-1000DM, the HCL-7000DX-M is intended for medium-voltage current measurement applications.

Important Note: Bluetooth connectivity is supported with dedicated MDU series display units, but connection to the manufacturer's app is currently unavailable.

Key Features of HCL-7000DX-M Digital Clamp Current Tester for Medium Voltage

  • AC Current Ranges: 20 A / 200 A / 600 A (Auto)
  • Maximum Circuit Voltage: AC 23 kV (with a hot stick longer than 1 m)
  • CT Inside Diameter: 35 mm
  • Applicable Frequency: 50–60 Hz
  • Bluetooth Connectivity: Remote measurement display via dedicated MDU series units
View AllClose

Additional Information

Measuring function:
AC load current
Resolution:
See the table in description tab
Measuring ranges:
20A/ 200A/ 600A (Auto)
Accuracy:
See the table in description tab
CT shape:
Round shape
CT Inside diameter:
35mm
Applicable frequency:
50~60Hz
Sampling rate:
Two times / second
Power supply:
AAA(LR03) size battery×3
Dimension:
W66×H215.4×D55mm(Not including the universal joint)
Insulation resistance:
100MΩ or more by DC 1000V insulation tester (Between hot stick grip to the universal joint)
Limitation of circuit voltage:
AC 23kV when connected to the hotstick with more than 1m.
Withstanding voltage:
AC 24kV when connected to the hotstick with more than 1m.
Operating temp & humidity range:
0℃~40℃, 80%RH or less
Storage temp & humidity range:
-10℃~60℃, 80%RH or less