Multi Measuring Instruments
HCL-36UX slim ver HCL-36UX slim ver Digital Clamp Current Tester for Medium Voltage
- SKU:
- HCL-36UX-slim
- Weight:
- 890.00 Grams
Description
HCL-36UX slim ver HCL-36UX slim ver Digital Clamp Current Tester for Medium Voltage
The HCL-36UX slim ver is a digital AC clamp current tester designed for medium-voltage overhead distribution lines. Its open U-shaped current transformer with a 55.4 mm inside diameter enables load current measurement without mechanically clamping around the conductor. It measures AC currents up to 3000 A with automatic range selection and an accuracy of ±1% rdg ±2 dgt.
Bluetooth connectivity enables measurement readings to be displayed on a smartphone, while the Multi-Tracer app supports harmonic current measurement up to the 25th order without cutting the conductor insulation. Measurement data can also be stored on a cloud server along with GPS location, temperature, date and time.
The drop-impact-resistant structure, IP52 protection and optional MDU-100X or MDU-200X display units provide additional flexibility for field measurements.
Key Features of HCL-36UX slim ver HCL-36UX slim ver Digital Clamp Current Tester for Medium Voltage
- AC load current measurement up to 3000 A with auto-ranging
- Open U-shaped CT with 55.4 mm inside diameter
- Measurement accuracy of ±1% rdg ±2 dgt
- Harmonic current measurement up to the 25th order via Multi-Tracer app
- Bluetooth connectivity for smartphone display and cloud data storage
Documents
Instruction Manual: e-ma-HCL-36UX slim ver1.30.pdf
Additional Information
Measuring function: |
AC load current |
CT shape: |
Type U |
CT Inside diameter: |
55.4mm |
Measuring range: |
AC 1~330A/3000A (2 range Auto) |
Accuracy: |
±1%rdg±2dgt |
Minimum resolution: |
0.1A |
Measurable harmonics: |
Fundamental to 25th harmonics current by using our APP"Multi-Tracer" |
Applicable frequency: |
50~60Hz |
Power supply: |
AA size battery×4 |
Dimension: |
W179.6×H400×D90.4mm |
Accessories: |
MDU-100X/MDU-200X (display unit) |
Sampling rate: |
Two times / second |
Insulation resistance: |
100MΩ or more by DC 1000V insulation tester (Between hot stick connector and core of CT) |
Limitation of circuit voltage: |
AC36kV |
Protection standard: |
IP54 |
Withstanding voltage: |
AC28.8kV/5min with slim ver(Between CT and the hotstick grip) |