Multi Measuring Instruments
RLM-10+ Flexible Leakage/Line Current Tester
- SKU:
- RLM-10
- Weight:
- 1,900.00 Grams
Description
RLM-10+ Flexible Leakage/Line Current Tester
This Flexible Split-Core AC Current and Leakage Current Meter is designed to measure AC line current and leakage current across four manually selectable ranges: 1000mA, 10A, 100A, and 1000A at 50/60 Hz. Its flexible split-core sensor features a 210 mm inside diameter, allowing current measurement around conductors without disconnecting them.
The instrument uses a dual integration measuring method and features a 9999-count LCD with backlight, Data Hold, and a selectable 150 Hz low-pass filter for reducing high-frequency signal components. A DC 100mV full-scale analog output is provided for each measuring range, with support for external recording equipment. The meter also includes automatic power-off after approximately 10 minutes, which is disabled when the recorder cable is connected.
Accuracy Specifications
Accuracy conditions: 23℃ ±5℃, less than 80%RH
| Function | Range / Resolution | Accuracy | Maximum Input / Protection |
|---|---|---|---|
| AC Current (50/60 Hz) | 1000 mA / 0.1 mA | ±3% rdg ±5 dgt | Not specified |
| 10 A / 0.001 A | ±2.5% rdg ±5 dgt | ||
| 100 A / 0.01 A | ±2.5% rdg ±5 dgt | ||
| 1000 A / 0.1 A | ±2.5% rdg ±5 dgt | ||
| Signal Output | DC 100mV full scale (each range) | ±2% F.S. | Not specified |
Key Features –RLM-10+ Flexible Leakage/Line Current Tester
- Dual Current Measurement: Measures AC leakage current and AC line current at 50/60 Hz.
- Four Selectable Ranges: 1000mA, 10A, 100A, and 1000A with manual rotary switch selection.
- Flexible Split-Core Sensor: 210 mm inside diameter for measurements around conductors without disconnecting them.
- Measurement Accuracy: ±3% rdg ±5 dgt at 1000mA and ±2.5% rdg ±5 dgt at 10A, 100A, and 1000A.
- Signal Output and Filtering: DC 100mV full-scale output for each range and selectable 150 Hz low-pass filter.
Documents
Catalog: e-ma-RLM-10+CE.pdf
Instruction Manual: e_ma_m-RLM-10+(K) ver1.00.pdf
Additional Information
Measuring method: |
Dual slope integration mode |
Accuracy: |
See accuracy specifications in description tab |
Display: |
LCD, max. 3200 count with annunciators |
Measurement range: |
AC20mA/200mA/2A/20A/200A/1000A/Auto |
Auto power off function: |
Approx. 10 minutes after power on (this function is cancelled in case of using recorder cable for signal output) |
Over range indication: |
"OL" mark on LCD |
Data hold indication: |
"DH" mark on LCD with data hold value |
Low battery indication: |
"Battery" icon on LCD |
Sampling rate: |
2 times/sec |
Storage temperature: |
-10~60℃, < 70%RH without condensation |
Power supply: |
1.5V (“AA” size, UM-3) x 6 |
Dimension: |
159(W)×105(H)×53(D) mm |
Accessories: |
Battery (UM-3 x 6), Instruction Manual , Carrying Case |
Influence of Residual Current: |
Less than 0.25A (at AC 50A, the point where influence is most receivable) |
Withstanding Voltage: |
AC 2200V/1 minute |
Limitation of circuit voltage: |
Less than AC 600V |
Measuring function: |
AC load current, AC leakage current |
Length of Lead Wire: |
Approx. 2m between CT and Measuring Part |
Filter function: |
Low pass filter : 150Hz |
AC Conversion: |
AC coupled true rms responding |
Circuit Voltage: |
Less than AC 600V |
Backlight Function: |
By pressing this switch, back light appears on LCD display and will get off by pressing this switch once again. |
Signal Output: |
DC 100mV full scale to each range (Output impedance : less than 10KΩ) |