null
Autonics

Multi-Function Analog Timer - AT11DN

(No reviews yet) Write a Review
SKU:
AT11DN
Weight:
500.00 Grams

Sold Out

Description

Product Overview

The Autonics AT11DN is a multi function analog timer designed for industrial control applications requiring selectable timing modes and relay-based switching. It supports a time setting range from 0.05 seconds to 100 hours, Signal ON Start operation, multiple timing modes including ON Delay, OFF Delay, ON/OFF Delay, Flicker, and Interval, and a DPDT (2 Form C) time-limit relay output. The standard model features a universal 100–240 VAC / 24–240 VDC power supply and an 11-pin plug-in configuration for panel-mounted control systems.

 

Key Features

  • Multi-function timer with selectable timing operation modes
  • Signal ON Start timing operation
  • Supports Signal ON Delay, Signal OFF Delay, Signal ON-OFF Delay, Flicker, and Interval output modes
  • Time setting range from 0.05 seconds to 100 hours
  • Universal power supply: 100–240 VAC, 50/60 Hz or 24–240 VDC
  • 11-pin plug-in configuration
  • No-voltage input for START, RESET, and INHIBIT control signals
  • Time Limit DPDT (2 Form C) relay output
  • CE, UKCA, cRUus, RoHS, and EAC compliance marks shown in the manufacturer’s product information

 

Ordering Information

The Autonics AT11DN model code identifies the timer series, plug configuration, output type, and standard power-supply version.

 

Model Code Description
AT Analog Timer series
11 11-pin plug type
DN Time Limit DPDT (2 Form C) relay output
No Mark Universal power supply: 100–240 VAC, 50/60 Hz or 24–240 VDC

 

Parameter AT11DN Configuration
Series AT Analog Timer
Model AT11DN
Output Configuration Time Limit DPDT (2 Form C)
Plug Configuration 11-pin plug type
Power Supply 100–240 VAC, 50/60 Hz or 24–240 VDC universal
Included Accessory Mounting bracket

 

Socket requirement: The compatible PG-11 or PS-11(N) 11-pin socket is sold separately and is not included with the timer.

 

Technical Specifications

 

Product Identity

Parameter AT11DN Specification
Model AT11DN
Function Multi Function Timer
Control Time Setting Range 0.05 sec to 100 hours
Time Operation Signal ON Start
Return Time Max. 100 ms
Plug Type 11-pin plug type

 

Power Supply

AT11DN Version Power Supply
AT11DN 100–240 VAC, 50/60 Hz or 24–240 VDC universal
AT11DN-1 12 VDC
AT11DN-2 24 VAC, 50/60 Hz or 24 VDC

 

Parameter Specification
Allowable Voltage Range 90 to 110% of rated voltage

 

Power Consumption

Power Supply Maximum Power Consumption
100–240 VAC Max. 3.5 VA
24–240 VDC Max. 1.5 W
24 VAC Max. 4 VA
24 VDC Max. 1.5 W
12 VDC Max. 1 W

 

Control Inputs

Parameter AT11DN Specification
Input Functions START, RESET, INHIBIT
Input Method No-voltage input
Minimum Input Signal Width Approx. 50 ms

 

Control Output

Parameter AT11DN Specification
Contact Type Time Limit DPDT, 2 Form C
Contact Capacity at AC 250 VAC, 5 A resistive load
Contact Capacity at DC 24 VDC, 5 A resistive load

 

Relay Life Cycle

Parameter AT11DN Specification
Mechanical Life Minimum 10,000,000 operations
Electrical Life Minimum 100,000 operations at 250 VAC, 5 A resistive load

 

Timing Error Characteristics

Parameter AT11DN Specification
Repeat Error Max. ±0.2% ±10 ms
Setting Error Max. ±5% ±50 ms
Voltage Error Max. ±0.5%
Temperature Error Max. ±2%

 

Electrical Insulation

Parameter AT11DN Specification
Insulation Resistance 100 MΩ at 500 VDC megger
Dielectric Strength 2,000 VAC, 50/60 Hz for 1 minute

 

Environmental Conditions

Parameter AT11DN Specification
Operating Ambient Temperature -10 to 55°C
Storage Temperature -25 to 65°C
Operating Ambient Humidity 35 to 85% RH
Storage Humidity 35 to 85% RH
Environmental Condition No freezing or condensation

 

Approval

Parameter AT11DN Specification
Approvals Shown in the Instruction Manual CE, cRUus

 

 

Time Setting Range

The Autonics AT11DN provides an overall adjustable timing range from 0.05 seconds to 100 hours. The time unit and range are selected from the front-panel controls, and the required time is then set using the adjustment dial.

 

Time Unit Available Range Selections Adjustable Coverage
Seconds 0.5, 1.0, 5, 10 0.05 to 10 sec
Minutes 0.5, 1.0, 5, 10 0.05 to 10 min
Hours 0.5, 1.0, 5, 10 0.05 to 10 hours
10-Hour Scale 0.5, 1.0, 5, 10 0.5 to 100 hours

 

Overall Adjustable Timing Range: 0.05 seconds to 100 hours.

 

 

Wiring and Control Interface

The AT11DN uses an 11-pin plug-in connection with dedicated terminals for the power supply, control inputs, and Time Limit DPDT relay output.

 

Control Input Functions

Input Function
START Starts the timing operation.
RESET Resets the timer and clears the current timing cycle.
INHIBIT Temporarily pauses the timing operation while retaining the elapsed time.

 

The control inputs operate as no-voltage inputs, with a minimum input signal width of approximately 50 ms.

 

 

Dimensions

The Autonics AT11DN uses a standard 48 × 48 mm front-panel format for panel installation. All dimensions are in millimetres.

 

Main Mechanical Dimensions

Parameter Dimension
Front Panel Width 48 mm
Front Panel Height 48 mm
Front Bezel Width 48.6 mm
Main Body Width 44.9 mm
Main Body Height 44.8 mm
Body Depth 50 mm

 

Panel Cut-out Dimensions

Parameter Specification
Required Panel Cut-out 45 × 45 mm
Cut-out Tolerance +0.6 / 0 mm
Minimum Horizontal Installation Pitch 65 mm
Minimum Vertical Installation Pitch 65 mm

 

Data Sheet

You may be searching for this product's catalog. If so, please click to view the Autonics AT11DN datasheet.
View AllClose

Warranty Information

One Year Warranty
View AllClose

Additional Information

Operation method:
Time setting
Output Operation:
SIGNAL ON DELAY, SIGNAL OFF DELAY, SIGNAL ON-OFF DELAY, FLICKER, INTERVAL
Time operation:
SIGNAL ON START
Terminal:
11-pin plug
Power supply:
100-240VAC~, 24-240VDC
Setting range:
0.05 to 0.5 sec, 0.1 to 1 sec, 0.5 to 5 sec, 1 to 10 sec, 0.05 to 0.5 min, 0.1 to 1 min, 0.5 to 5 min, 1 to 10 min, 0.05 to 0.5 hour, 0.1 to 1 hour, 0.5 to 5 hour, 1 to 10 hour, 5 to 50 hour, 10 to 100 hour
Signal Input Method:
No-voltage input(NPN)
Control output:
Time-limit SPDT (1c): 2
View AllClose