null
Multi Measuring Instruments

M-140RMS Mini AC Leakage Current Clamp Tester

(No reviews yet) Write a Review
SKU:
M-140-RMS
Weight:
125.00 Grams

Sold Out

Description

M-140RMS Mini AC Leakage Current Clamp Tester

The MULTI M-140RMS Mini AC Leakage Current Clamp Tester is a compact True-RMS clamp meter designed to measure AC leakage current and AC current. It provides selectable measurement ranges for low-level leakage current and higher AC currents, with a 40 mm jaw opening and a maximum measurement range of 400 A.

The M-140RMS features a 3.5-digit LCD with a maximum reading of 3999, data hold, and automatic power-off after approximately 10 minutes. Its compact dimensions of 64 × 162 × 23 mm and approximate weight of 125 g make it suitable for portable measurement. The instrument complies with IEC 61010-1 and IEC 61010-2-032, with safety ratings of CAT II 600 V and CAT III 300 V.

Specification Value
Range AC 30/300mA/0.01mA/±1.2% rdg ± 5dgt
AC 30/300A/0.01A/0~200A : ±1.2% rdg ± 5dgt
200~250A : ±3.0% rdg ± 5dgt
250~300A : ±5.0% rdg ± 5dgt

Key Features –M-140RMS Mini AC Leakage Current Clamp Tester

  • True-RMS Measurement: Measures AC leakage current and AC current using the True-RMS method.
  • Wide Measurement Range: Supports AC leakage current measurement at 30/300 mA and AC current measurement up to 400 A.
  • 40 mm Jaw Opening: Features a 40 mm CT opening for current measurement.
  • Reduced Magnetic Interference: Designed to minimize the influence of external magnetic fields.
  • Compact and Lightweight: Measures 64 × 162 × 23 mm and weighs approximately 125 g, with data hold and automatic power-off functions.
View AllClose

Additional Information

Safety standard:
IEC 61010-1, IEC 61010-2-032 Installation CategoryⅡ600V or CategoryⅢ300V.
E.M.C. standard:
EN 61326
Measuring method:
True-RMS
Range:
AC 0~40mA/400mA, 40A/400A, 2 range manual
Accuracy:
23℃±5℃ 80%RH or less (50/60Hz)
Range:
see the table in description tab
Jaw opening capability:
40mmφ
Display:
3.5 digit LCD, max. reading of 3999Over range indication
Data hold indication:
"DH" mark on LCD
Low battery indication:
"Battery" mark on LCD
Operating Temperature:
0℃ to 40℃, 80%RH max. ( Without condensation )
Storage Temperature:
-10℃ to 60℃, 70%RH max. ( Without condensation )
Auto power off:
Approx. 10 minutes later after power on
Power supply:
1.55V (SR-44, LR-44)×2
Battery life:
Approx. 50 hours(LR-44)
Power consumption:
3mA
Withstanding Voltage:
AC 3700V 1 minute max. (Between the core of CT and outer case)
Size:
64(W)×162(H)×23(D)mm
Sampling:
2 times/sec (Digital display) || 12 times/sec (Bar graph display)
Accessories:
Soft case:1 || Instruction manual:1 || Batteries LR-44(1.55V):2
View AllClose