null

DATEXEL Temperature Transmitter Device Din Rail Temperature Transmitters DAT2015

Write a Review
SKU:
DAT2015
MPN:
DAT2015
Weight:
100.00 Grams
Shipping:
Calculated at Checkout
$225.00

Description

DAT2015 from Datexel is a Universal Temperature Transmitter, Din Rail mount Temperature/signal transmitter with PC programmability. The input can be thermocouples, RTD, mA, V, mV, Resistor.nce and potentiometer. The DAT2015 will linearize the temperature input and provide a 4-20mA output signal. It is accurate to 0.1% full scale and has less than 0.01%/°f thermal drift.

The DAT2015 is programmable by PC based software which has been developed by DATEXEL to be user-friendly. For resistance and RTD's sensors, it is possible to program the cable compensation for 3 or 4 wires. It is possible to set the minimum and maximum values of the input and output range at any point of the scale, keeping the minimum span shown in the Data-sheet. Also, a high burn out alarm or low burn out alarm is selectable. The DAT2015 is In compliance with the standard 89/336/CEE on the Electromagnetic Compatibility. DAT2015 is housed in a plastic enclosure of 12.5 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards and is able to measure and linearize the standard thermocouples with internal cold junction compensation.

DAT2015 from Datexel comes with the following features:

  • Configurable input for RTD, TC, mV, V, mA, Resistor.nce and Potentiometer.
  • 4 ÷ 20 mA configurable output on the current loop.
  • Configurable by Personal Computer.
  • High accuracy.
  • On-field reconfigurable.
  • EMC compliant with CE mark.
  • Suitable for DIN rail mounting in compliance with EN-50022 and EN50035.

Brand Information

Datexel products are made to the very highest standards and all products carry the CE mark, and since March 2015 all slim-line products and DAT3000 modules carry the UL and CSA mark. Datexel obtained ISO 9001 in 1996 and now has the current standard UNI EN ISO 9001:2000 (issued in 2001). Datexel's signal conditioners also carry the ATEX 94/9/EC approval for safe environments. In July 2006, Datexel confirmed its products to the RoHS Directive Standard (2002/95/EC) which imposes restrictions on the use of dangerous substances for the manufacturing of electric and electronic equipment. Situated in Jupiter, Florida USA.

Data Sheet

To View Data Sheet Please Click Here
View AllClose

Warranty Information

One year warranty.
View AllClose

Additional Information

Input Calibration:
none
RTD:
> of ±0.1% f.s. or ±0.2°C.
Low Resistor.nce:
> of ±0.1% f.s. or ±0.15 Ω.
High Resistor.nce:
> of ±0.2% f.s. or ±1 Ω.
mV, TC:
> of ±0.1% f.s. or ±18 uV.
Volt:
> of ±0.1% f.s. or ± 2 mV.
mA:
> of ±0.1% f.s. or ± 6 uA.
Output Calibration:
none
current:
± 7 uA.
Input impedance:
none
TC mV:
>= 10 MΩ.
Volt:
>= 1 MΩ.
Current:
~ 50 Ω.
Linearity:
none
TC:
± 0.2 % f.s.
RTD:
± 0.1 % f.s.
Line Resistor.nce influence:
none
TC, mV:
<=0.4 uV/Ohm.
RTD 3-wired:
0.05%/Ω (50 Ω balanced max.).
RTD 4-wired:
0.005%/Ω (100 Ω balanced max.).
RTD excitation current (typical):
0.350 mA.
CJC comp.:
± 0.5°C.
Thermal Drift 1:
none
Full Scale:
± 0.01% / °C.
CJC:
± 0.01% / °C.
Burnout values:
none
Max. value:
About 22.5 mA.
Min. value:
About 3.6 mA.
Response time (10÷ 90%):
About 400ms.
Power supply:
none
Power supply voltage:
10…32VDC.
Reverse polarity protection:
60VDC max.
Temp. and humidity:
none
Operative temperature:
-20°C …+70°C.
Storage temperature:
-40°C …+85°C.
Humidity (not condensed):
0 …90 %.
Housing:
none
Material:
Self-extinguish plastic.
Mounting:
DIN rail In compliance with EN-50022 and EN-50035.
Weight:
About 90g.
EMC (for industrial environments):
none
Immunity:
EN 61000-6-2.
Emission:
EN 61000-6-4.
View AllClose