null
DF Electric

Cylindrical fuse link 14×51 aM

(No reviews yet) Write a Review
SKU:
14-51 aM
Weight:
18.00 Grams

Sold Out

Description

DF Electric 14×51 mm aM Cylindrical Fuse Link

The DF Electric 14×51 aM is a low-voltage cylindrical fuse link designed for short-circuit protection in motor circuits. The fuse links are available in 14×51 mm size, with rated currents from 0.25 to 50 A and rated voltages of 690 V AC, 500 V AC, and 400 V AC, depending on the current rating and reference.

They are available without an indicator, with an indicator, or with a striker, and comply with IEC/EN 60269-1 and IEC/EN 60269-2 standards

Dimensions

Dimension

A B C D E
14,3 51 13 8 3,7

DF Electric 14×51 mm aM Cylindrical Fuse Link Range and Reference Numbers

SIZE Un (V) In (A) REFERENCE
WITHOUT INDICATOR WITH INDICATOR
14×51 690 0.25 441031 -
0.5 441000 -
1 441001 441101
2 441002 441102
4 441004 441104
6 441006 441106
8 441008 441108
10 441010 441110
12 441012 441112
16 441016 441116
20 441020 441120
25 441025 441125
500 32 441032 441132
40 441040 441140
45 441045 441145
400 50 441050 441150

DF Electric 14×51 mm aM Cylindrical Fuse Link Range with Striker

SIZE Un (V) In (A) REFERENCE
      WITH STRIKER
14×51 500 1 441201
2 441202
4 441204
6 441206
8 441208
10 441210
12 441212
16 441216
20 441220
25 441225
32 441232
40 441240
45 441245
400 50 441250

Power Dissipation and I²t Values

Rated Current (A) Reference * Power Dissipation (W) Prearcing I²t (A²s) I²t 690 V (A²s) I²t 500 V (A²s) I²t 400 V (A²s)
0.25 441031 0.41 4.0 15.0 10.4 8.6
0.5 441000 0.69 6.5 22.0 15.7 13.2
1 441001 0.14 9.5 30.0 21.9 18.5
2 441002 0.24 40 140 99 83
4 441004 0.45 90 300 215 181
6 441006 0.42 120 425 300 250
8 441008 0.70 220 750 535 448
10 441010 0.53 300 1400 916 733
12 441012 0.88 380 1800 1173 936
16 441016 1.16 550 3500 2103 1608
20 441020 1.23 950 5000 3165 2488
25 441025 1.46 1300 8000 4851 3728
32 441032 2.04 2500 12000 7791 6207
40 441040 2.60 4500 20000 13263 10685
45 441045 2.85 8000 28000 19831 16538
50 441050 2.90 10000 32000 23230 19626

* Same data for INDICATOR and STRIKER range.

t-I characteristics

t-I characteristics

Cut-off characteristics

Cut-off characteristics

Documents

DF Electric 14×51 mm aM Cylindrical Fuse Link Datasheet

View AllClose

Additional Information

Rated voltage:
690V +5% | 500V +10% | 400V +10%
Rated currents:
0,25A...50A
Rated breaking capacity:
80kA (690V) | 120kA (500V/400V)
Operating class:
aM
Rated frequency:
42…62Hz
Storage temperature:
-40°C ... 90°C
Operating temperature:
-40°C ... 80°C
View AllClose